Multilevel STATCOM with Third Harmonic Elimination on the DC Link Capacitor Voltages

Abstract
Simulation studies, confirmed by laboratory experiments, show that the undesirable third harmonic inherently present on the DC link capacitor voltages of multilevel converters can be eliminated by a 6-phase configuration in a shunt multilevel STATCOM. The principle can be extended to eliminate the residual sixth harmonic by configuring a 12-phase STATCOM
Description
Full text available at http://ieeexplore.ieee.org/xpl/articleDetails.jsp?arnumber=616743&newsearch=true&queryText=.QT.Multilevel%20STATCOM%20with%20Third%20Harmonic%20Elimination%20on%20the%20DC%20Link%20Capacitor%20Voltages
Keywords
capacitors, harmonic distortion, power convertors, power system harmonics, static VAr compensators
Citation
Mwinyiwiwa, B., Wolanski, Z. and Ooi, B.T., 1997, June. Multilevel STATCOM with third harmonic elimination on the DC link capacitor voltages. In Power Electronics Specialists Conference, 1997. PESC'97 Record., 28th Annual IEEE (Vol. 1, pp. 317-322). IEEE.