Performance Evaluation of DSTATCOM for 180 km 33 kV Feeder from Shinyanga to Bariadi in Tanzania
Loading...
Date
2021-12-01
Journal Title
Journal ISSN
Volume Title
Publisher
Jordan Journal of Electrical Engineering (JJEE)
Abstract
Tanzanian medium voltage of 33 kV and 11 kV is used as the system voltage for
primary distribution feeders. The design of these feeders is mainly radial topology. Due to the
nature of dispersed and scattered load centers (towns) in Tanzania [1], the feeders have to run
over long routes, such as the 180 km 33 kV Shinyanga–Bariadi line [2]. The feeder runs all
this distance without any voltage control compensators; thus at the receiving end, it suffers a
voltage drop of more than 7%. The result of this voltage drop is failing to start the large water
pumping motors connected close to the end of the feeder, especially during peak load.
Voltage improvement can be achieved using the volt-ampere reactive (VAR) compensation,
series compensation and flexible alternating current transmission system (FACTS). However,
these methods cannot handle dynamic voltage changes effectively. Therefore, fast reactive
power compensation is necessary [3]. Distribution static synchronous compensator
(DSTATCOM) can provide fast and continuous reactive power (đť‘„) compensation to control
the voltage of the feeder. However, off-the-shelf DSTATCOM cannot be used without the
knowledge of the line parameters, control, power and other data of the feeder. Therefore, this
paper proposes the use of the DSTATCOM for the 180 km 33 kV feeder for the Shinyanga–
Bariadi line.